Industrial Controls & Automation

LC1F265R7

LC1-F265R7 Telemecanique – Contactor 3 poles AC3 265A, 440Vca

$1,050.00

Main
range TeSys
product name TeSys F
product or component type Contactor
device short name LC1F
contactor application Motor control
Resistive load
utilisation category AC-3
AC-1
AC-4
poles description 3P
power pole contact composition 3 NO
[Ue] rated operational voltage <= 1000 V AC-1
<= 690 V AC-3
<= 690 V AC-4
<= 460 V DC
[Ie] rated operational current 350 A (at <40 °C) at <= 440 V AC AC-1
265 A (at <55 °C) at <= 440 V AC AC-3
motor power kW 132 kW at 380…400 V AC 50/60 Hz (AC-3)
140 kW at 415 V AC 50/60 Hz (AC-3)
140 kW at 440 V AC 50/60 Hz (AC-3)
160 kW at 500 V AC 50/60 Hz (AC-3)
160 kW at 660…690 V AC 50/60 Hz (AC-3)
147 kW at 1000 V AC 50/60 Hz (AC-3)
75 kW at 220…230 V AC 50/60 Hz (AC-3)
51 kW at 400 V AC 50/60 Hz (AC-4)
[Uc] control circuit voltage 440 V AC 40…400 Hz
Complementary
[Uimp] rated impulse withstand voltage 8 kV
overvoltage category III
[Ith] conventional free air thermal current 350 A (at 40 °C)
rated breaking capacity 2120 A conforming to IEC 60947-4-1
[Icw] rated short-time withstand current 2200 A 40 °C – 10 s
1230 A 40 °C – 30 s
950 A 40 °C – 1 min
620 A 40 °C – 3 min
480 A 40 °C – 10 min
associated fuse rating 315 A aM at <= 440 V
400 A gG at <= 440 V
average impedance 0.3 mOhm – Ith 350 A 50 Hz
[Ui] rated insulation voltage 1000 V conforming to IEC 60947-4-1
1500 V conforming to VDE 0110 group C
power dissipation per pole 37 W AC-1
21 W AC-3
mounting support Plate
standards IEC 60947-4-1
EN 60947-1
EN 60947-4-1
IEC 60947-1
JIS C8201-4-1
product certifications RMRoS
CCC
BV
CB
ABS
LROS (Lloyds register of shipping)
DNV
UL
RINA
UKCA
connections – terminals Control circuit: screw clamp terminals 1 cable(s) 1…4 mm²flexible without cable end
Control circuit: screw clamp terminals 2 cable(s) 1…4 mm²flexible without cable end
Control circuit: screw clamp terminals 1 cable(s) 1…4 mm²flexible with cable end
Control circuit: screw clamp terminals 2 cable(s) 1…2.5 mm²flexible with cable end
Control circuit: screw clamp terminals 1 cable(s) 1…4 mm²solid without cable end
Control circuit: screw clamp terminals 2 cable(s) 1…4 mm²solid without cable end
Power circuit: bar 2 cable(s) – busbar cross section: 32 x 4 mm
Power circuit: lugs-ring terminals 1 cable(s) 240 mm²
Power circuit: connector 1 cable(s) 240 mm²
Power circuit: bolted connection
tightening torque Control circuit: 1.2 N.m
Power circuit: 35 N.m
control circuit voltage limits Operational: 0.85…1.1 Uc 40…400 Hz (at 55 °C)
Drop-out: 0.15…0.2 Uc 40…400 Hz (at 55 °C)
inrush power in VA 650 VA 40…400 Hz cos phi 0.9 (at 20 °C)
hold-in power consumption in VA 10 VA 40…400 Hz cos phi 0.9 (at 20 °C)
heat dissipation 8 W
operating time 40…65 ms closing
100…170 ms opening
mechanical durability 10 Mcycles
maximum operating rate 2400 cyc/h 55 °C
compatibility code LC1F
Environment
IP degree of protection IP20 front face with shrouds conforming to IEC 60529
IP20 front face with shrouds conforming to VDE 0106
protective treatment TH
ambient air temperature for operation -5…55 °C
ambient air temperature for storage -60…80 °C
permissible ambient air temperature around the device -40…70 °C
operating altitude 3000 m without derating
height 203 mm
width 201.5 mm
depth 213 mm
net weight 7.44 kg
Packing Units
Unit Type of Package 1 PCE
Number of Units in Package 1 1
Package 1 Weight 7.975 kg
Package 1 Height 25.5 cm
Package 1 width 25 cm
Package 1 Length 30 cm