Industrial Controls & Automation

LC1D09P7 IEC contactor
LC1D09P7 IEC contactor, TeSys Deca, nonreversing, 9A, 5HP at 480VAC
LC1D09P7 IEC contactor

LC1D09P7 IEC contactor, TeSys Deca, nonreversing, 9A, 3 phase, 3 NO, 230VAC 50/60Hz coil

LC1D09P7 IEC contactor, TeSys Deca, nonreversing, 9A, 5HP at 480VAC, up to 100kA SCCR, 3 phase, 3 NO, 230VAC 50/60Hz coil, open style

$60.00

TeSys D contactors have been designed for perfect integration into control systems. They can be used to create motor starters for almost any type of application. TeSys D contactors are available in 13 contactor ratings for inductive motor applications up to 150 full-load amps and resistive loads up to 200 amps. This 9A inductive 3 pole IEC contactor can be mounted on DIN rail or mounted directly to a panel. Contactors have both Horsepower and Kw motor rating for international acceptance. Contactor is rated for 20HP at 200-208VAC, 25HP at 240VAC, 60HP at 480VAC and 60HP at 600VAC three phase. Contactor is also rated for 7.5HP at 115VAC and 15HP at 240VAC single phase. When used with a 480VAC up to 35A circuit breaker, this contactor can have a SCCR up to 85kA. When used with up to a 600VAC 25A Class J or CC fuse, this contactor can have a SCCR up to 100kA. Contactor is supplied with a 230 VAC 50/60 Hz coil. Contactor has one normally open and one normally closed auxiliary contact built-in as standard. The NC contact is mirror certified. Screw clamp terminals are used for load and auxiliary connections. An extensive line of accessories makes it easy to meet the requirements of most applications. The contactor is 3.15 inches tall, 1.77 inches wide and 3.39 inches deep. It weighs 0.71 lbs. Contactor is certified to UL, CSA, IEC, CCC, EAC and Marine standards. Contactor also meets the requirements of RoHS/REACh making it a Green Premium product.

 

Specifications

Main
Range of Product TeSys Deca
Product or Component Type Contactor
Device short name LC1D
contactor application Resistive load
Motor control
Utilisation category AC-4
AC-1
AC-3
AC-3e
poles description 3P
[Ue] rated operational voltage Power circuit <= 690 V AC 25…400 Hz
Power circuit <= 300 V DC
[Ie] rated operational current 9 A (at <140.0000000000 °F (60 °C)) at <= 440 V AC AC-3 for power circuit
25 A (at <140.0000000000 °F (60 °C)) at <= 440 V AC AC-1 for power circuit
9 A (at <140.0000000000 °F (60 °C)) at <= 440 V AC AC-3e for power circuit
[Uc] control circuit voltage 230 V AC 50/60 Hz
Complementary
Motor power kW 2.2 kW at 220…230 V AC 50/60 Hz (AC-3)
4 kW at 380…400 V AC 50/60 Hz (AC-3)
4 kW at 415…440 V AC 50/60 Hz (AC-3)
5.5 kW at 500 V AC 50/60 Hz (AC-3)
5.5 kW at 660…690 V AC 50/60 Hz (AC-3)
2.2 kW at 400 V AC 50/60 Hz (AC-4)
2.2 kW at 220…230 V AC 50/60 Hz (AC-3e)
4 kW at 380…400 V AC 50/60 Hz (AC-3e)
4 kW at 415…440 V AC 50/60 Hz (AC-3e)
5.5 kW at 500 V AC 50/60 Hz (AC-3e)
5.5 kW at 660…690 V AC 50/60 Hz (AC-3e)
Maximum Horse Power Rating 1 hp at 230/240 V AC 50/60 Hz for 1 phase motors
2 hp at 200/208 V AC 50/60 Hz for 3 phase motors
2 hp at 230/240 V AC 50/60 Hz for 3 phase motors
5 hp at 460/480 V AC 50/60 Hz for 3 phase motors
7.5 hp at 575/600 V AC 50/60 Hz for 3 phase motors
0.33 hp at 115 V AC 50/60 Hz for 1 phase motors
Compatibility code LC1D
Pole contact composition 3 NO
Protective cover With
[Ith] conventional free air thermal current 25 A (at 140.0000000000 °F (60 °C)) for power circuit
10 A (at 140.0000000000 °F (60 °C)) for signalling circuit
Irms rated making capacity 250 A at 440 V for power circuit conforming to IEC 60947
140 A AC for signalling circuit conforming to IEC 60947-5-1
250 A DC for signalling circuit conforming to IEC 60947-5-1
Rated breaking capacity 250 A at 440 V for power circuit conforming to IEC 60947
[Icw] rated short-time withstand current 105 A 104.0000000000 °F (40 °C) – 10 s for power circuit
210 A 104.0000000000 °F (40 °C) – 1 s for power circuit
30 A 104.0000000000 °F (40 °C) – 10 min for power circuit
61 A 104.0000000000 °F (40 °C) – 1 min for power circuit
100 A – 1 s for signalling circuit
120 A – 500 ms for signalling circuit
140 A – 100 ms for signalling circuit
Associated fuse rating 10 A gG for signalling circuit conforming to IEC 60947-5-1
25 A gG at <= 690 V coordination type 1 for power circuit
20 A gG at <= 690 V coordination type 2 for power circuit
Average impedance 2.5 mOhm – Ith 25 A 50 Hz for power circuit
Power dissipation per pole 1.56 W AC-1
0.2 W AC-3
0.2 W AC-3e
[Ui] rated insulation voltage Power circuit 690 V IEC 60947-4-1
Power circuit 600 V CSA
Power circuit 600 V UL
Signalling circuit 690 V IEC 60947-1
Signalling circuit 600 V CSA
Signalling circuit 600 V UL
Overvoltage category III
Pollution degree 3
[Uimp] rated impulse withstand voltage 6 kV IEC 60947
Safety reliability level B10d = 1369863 cycles contactor with nominal load EN/ISO 13849-1
B10d = 20000000 cycles contactor with mechanical load EN/ISO 13849-1
Mechanical durability 15 Mcycles
Electrical durability 0.6 Mcycles 25 A AC-1 <= 440 V
2 Mcycles 9 A AC-3 <= 440 V
2 Mcycles 9 A AC-3e <= 440 V
Control circuit type AC 50/60 Hz standard
Coil technology Without built-in suppressor module
Control circuit voltage limits 0.3…0.6 Uc -40.0000000000…158.0000000000 °F (-40…70 °C) drop-out AC 50/60 Hz
0.8…1.1 Uc -40.0000000000…140.0000000000 °F (-40…60 °C) operational AC 50 Hz
0.85…1.1 Uc -40.0000000000…140.0000000000 °F (-40…60 °C) operational AC 60 Hz
1…1.1 Uc 140.0000000000…158.0000000000 °F (60…70 °C) operational AC 50/60 Hz
Inrush power in VA 70 VA 60 Hz cos phi 0.75 (at 68.0000000000 °F (20 °C))
70 VA 50 Hz cos phi 0.75 (at 68.0000000000 °F (20 °C))
Hold-in power consumption in VA 7.5 VA 60 Hz cos phi 0.3 (at 68.0000000000 °F (20 °C))
7 VA 50 Hz cos phi 0.3 (at 68.0000000000 °F (20 °C))
Heat dissipation 2…3 W at 50/60 Hz
Operating time 12…22 ms closing
4…19 ms opening
Maximum operating rate 3600 cyc/h 140.0000000000 °F (60 °C)
Maximum operating rate 3600 cyc/h at 60 °C
Connections – terminals Power circuit: screw clamp terminals 1 0.002…0.006 in² (1…4 mm²) – cable stiffness: flexible without cable end
Power circuit: screw clamp terminals 2 0.002…0.006 in² (1…4 mm²) – cable stiffness: flexible without cable end
Power circuit: screw clamp terminals 1 0.002…0.006 in² (1…4 mm²) – cable stiffness: flexible with cable end
Power circuit: screw clamp terminals 2 0.002…0.004 in² (1…2.5 mm²) – cable stiffness: flexible with cable end
Power circuit: screw clamp terminals 1 0.002…0.006 in² (1…4 mm²) – cable stiffness: solid without cable end
Power circuit: screw clamp terminals 2 0.002…0.006 in² (1…4 mm²) – cable stiffness: solid without cable end
Control circuit: screw clamp terminals 1 0.002…0.006 in² (1…4 mm²) – cable stiffness: flexible without cable end
Control circuit: screw clamp terminals 2 0.002…0.006 in² (1…4 mm²) – cable stiffness: flexible without cable end
Control circuit: screw clamp terminals 1 0.002…0.006 in² (1…4 mm²) – cable stiffness: flexible with cable end
Control circuit: screw clamp terminals 2 0.002…0.004 in² (1…2.5 mm²) – cable stiffness: flexible with cable end
Control circuit: screw clamp terminals 1 0.002…0.006 in² (1…4 mm²) – cable stiffness: solid without cable end
Control circuit: screw clamp terminals 2 0.002…0.006 in² (1…4 mm²) – cable stiffness: solid without cable end
Tightening torque Power circuit 15.05 lbf.in (1.7 N.m) screw clamp terminals flat Ø 6 mm
Power circuit 15.05 lbf.in (1.7 N.m) screw clamp terminals Philips No 2
Control circuit 15.05 lbf.in (1.7 N.m) screw clamp terminals flat Ø 6 mm
Control circuit 15.05 lbf.in (1.7 N.m) screw clamp terminals Philips No 2
Control circuit 15.05 lbf.in (1.7 N.m) screw clamp terminals pozidriv No 2
Power circuit 15.05 lbf.in (1.7 N.m) screw clamp terminals pozidriv No 2
Auxiliary contact composition 1 NO + 1 NC
Auxiliary contacts type Mechanically linked 1 NO + 1 NC IEC 60947-5-1
Mirror contact 1 NC IEC 60947-4-1
Signalling circuit frequency 25…400 Hz
Minimum switching voltage 17 V for signalling circuit
Minimum switching current 5 mA for signalling circuit
Insulation resistance > 10 MOhm for signalling circuit
Non-overlap time 1.5 ms on de-energisation between NC and NO contact
1.5 ms on energisation between NC and NO contact
Mounting Support Rail
Plate
Environment
Standards CSA C22.2 No 14
EN 60947-4-1
EN 60947-5-1
IEC 60947-4-1
IEC 60947-5-1
UL 60947-4-1
IEC 60335-1:Clause 30.2
IEC 60335-2-40:Annex JJ
UL 60335-2-40:Annex JJ
CSA C22.2 No 60947-4-1
Product Certifications UL
CCC
CSA
Marine
UKCA
EAC
CB Scheme
IP degree of protection IP20 front face IEC 60529
Protective treatment THIEC 60068-2-30
Climatic withstand IACS E10 exposure to damp heat
IEC 60947-1 Annex Q category D exposure to damp heat
Permissible ambient air temperature around the device -40.0000000000…140.0000000000 °F (-40…60 °C)
140.0000000000…158.0000000000 °F (60…70 °C) with derating
Operating altitude 0…9842.52 ft (0…3000 m)
Fire resistance 1562.0000000000 °F (850 °C) IEC 60695-2-1
Flame retardance V1 conforming to UL 94
Mechanical robustness Vibrations contactor open 2 Gn, 5…300 Hz)
Vibrations contactor closed 4 Gn, 5…300 Hz)
Shocks contactor open 10 Gn for 11 ms)
Shocks contactor closed 15 Gn for 11 ms)
Height 3.03 in (77 mm)
Width 1.8 in (45 mm)
Depth 3.4 in (86 mm)
Net Weight 0.71 lb(US) (0.32 kg)
Ordering and shipping details
Category US10I1222354
Discount Schedule 0I12
GTIN 3389110348903
Returnability Yes
Country of origin ID