Industrial Controls & Automation

LC1D150M7

LC1D150M7 – TeSys D Contactor – 3P(3 NO) – AC-3 – <= 440 V 150 A – 220 V AC 50/60 Hz coil.

$460.00

Main
range
TeSys
product name
TeSys D
product or component type
Contactor
device short name
LC1D
contactor application
Motor control
Resistive load
utilisation category
AC-3
AC-4
AC-1
poles description
3P
power pole contact composition
3 NO
[Ue] rated operational voltage
Power circuit: <= 1000 V AC 25…400 Hz
Power circuit: <= 300 V DC
[Ie] rated operational current
200 A (at <60 °C) at <= 440 V AC AC-1 for power circuit
150 A (at <60 °C) at <= 440 V AC AC-3 for power circuit
motor power kW
40 kW at 220…230 V AC 50/60 Hz (AC-3)
75 kW at 380…400 V AC 50/60 Hz (AC-3)
80 kW at 415…440 V AC 50/60 Hz (AC-3)
90 kW at 500 V AC 50/60 Hz (AC-3)
100 kW at 660…690 V AC 50/60 Hz (AC-3)
75 kW at 1000 V AC 50/60 Hz (AC-3)
22 kW at 400 V AC 50/60 Hz (AC-4)
motor power HP (UL / CSA)
40 hp at 200/208 V AC 50/60 Hz for 3 phases motors
50 hp at 230/240 V AC 50/60 Hz for 3 phases motors
100 hp at 460/480 V AC 50/60 Hz for 3 phases motors
125 hp at 575/600 V AC 50/60 Hz for 3 phases motors
control circuit type
AC at 50/60 Hz
[Uc] control circuit voltage
220 V AC 50/60 Hz
auxiliary contact composition
1 NO + 1 NC
[Uimp] rated impulse withstand voltage
8 kV conforming to IEC 60947
overvoltage category
III
[Ith] conventional free air thermal current
200 A (at 60 °C) for power circuit
Irms rated making capacity
140 A AC for signalling circuit conforming to IEC 60947-5-1
250 A DC for signalling circuit conforming to IEC 60947-5-1
1660 A at 440 V for power circuit conforming to IEC 60947
rated breaking capacity
1400 A at 440 V for power circuit conforming to IEC 60947
[Icw] rated short-time withstand current
250 A 40 °C – 10 min for power circuit
580 A 40 °C – 1 min for power circuit
1200 A 40 °C – 10 s for power circuit
1400 A 40 °C – 1 s for power circuit
100 A – 1 s for signalling circuit
120 A – 500 ms for signalling circuit
140 A – 100 ms for signalling circuit
associated fuse rating
10 A gG for signalling circuit conforming to IEC 60947-5-1
315 A gG at <= 690 V coordination type 1 for power circuit
250 A gG at <= 690 V coordination type 2 for power circuit
average impedance
0.6 mOhm – Ith 200 A 50 Hz for power circuit
[Ui] rated insulation voltage
Power circuit: 600 V CSA certified
Power circuit: 600 V UL certified
Power circuit: 1000 V conforming to IEC 60947-4-1
Signalling circuit: 690 V conforming to IEC 60947-1
Signalling circuit: 600 V CSA certified
Signalling circuit: 600 V UL certified
electrical durability
0.85 Mcycles 150 A AC-3 at Ue <= 440 V
1 Mcycles 200 A AC-1 at Ue <= 440 V
power dissipation per pole
24 W AC-1
13.5 W AC-3
safety cover
With
mounting support
Rail
Plate
standards
CSA C22.2 No 14
EN 60947-4-1
EN 60947-5-1
IEC 60947-4-1
IEC 60947-5-1
UL 508
product certifications
CCC
LROS (Lloyds register of shipping)
GL
GOST
RINA
CSA
BV
UL
DNV
connections – terminals
Control circuit: screw clamp terminals 2 cable(s) 1…2.5 mm²flexible with cable end
Control circuit: screw clamp terminals 1 cable(s) 1…2.5 mm²flexible with cable end
Control circuit: screw clamp terminals 1 cable(s) 1…2.5 mm²flexible without cable end
Control circuit: screw clamp terminals 2 cable(s) 1…2.5 mm²flexible without cable end
Control circuit: screw clamp terminals 1 cable(s) 1…2.5 mm²solid without cable end
Control circuit: screw clamp terminals 2 cable(s) 1…2.5 mm²solid without cable end
Power circuit: connector 1 cable(s) 10…120 mm²flexible without cable end
Power circuit: connector 2 cable(s) 10…50 mm²flexible without cable end
Power circuit: connector 1 cable(s) 10…120 mm²flexible with cable end
Power circuit: connector 2 cable(s) 10…50 mm²flexible with cable end
Power circuit: connector 1 cable(s) 10…120 mm²solid without cable end
Power circuit: connector 2 cable(s) 10…50 mm²solid without cable end
tightening torque
Control circuit: 1.2 N.m – on screw clamp terminals – with screwdriver flat Ø 6 mm
Control circuit: 1.2 N.m – on screw clamp terminals – with screwdriver Philips No 2
Power circuit: 12 N.m – on connector hexagonal screw head 4 mm
operating time
20…35 ms closing
40…75 ms opening
safety reliability level
B10d = 1369863 cycles contactor with nominal load conforming to EN/ISO 13849-1
B10d = 20000000 cycles contactor with mechanical load conforming to EN/ISO 13849-1
mechanical durability
8 Mcycles
maximum operating rate
1200 cyc/h 60 °C
Complementary
coil technology
Built-in bidirectional peak limiting diode suppressor
control circuit voltage limits
Drop-out: 0.3…0.5 Uc AC 50/60 Hz (at 55 °C)
Operational: 0.8…1.15 Uc AC 50/60 Hz (at 55 °C)
inrush power in VA
280…350 VA 60 Hz cos phi 0.9 (at 20 °C)
280…350 VA 50 Hz cos phi 0.9 (at 20 °C)
hold-in power consumption in VA
2…18 VA 60 Hz cos phi 0.9 (at 20 °C)
2…18 VA 50 Hz cos phi 0.9 (at 20 °C)
heat dissipation
3…4.5 W at 50/60 Hz
auxiliary contacts type
type mechanically linked 1 NO + 1 NC conforming to IEC 60947-5-1
type mirror contact 1 NC conforming to IEC 60947-4-1
signalling circuit frequency
25…400 Hz
minimum switching current
5 mA for signalling circuit
minimum switching voltage
17 V for signalling circuit
non-overlap time
1.5 ms on de-energisation between NC and NO contact
1.5 ms on energisation between NC and NO contact
insulation resistance
> 10 MOhm for signalling circuit