LC1F500R7
LC1F500R7 – TeSys F Contactor – 3P (3 NO) – AC-3 – <= 440 V 500 A – coil 440 V AC.
$1,800.00
range |
TeSys
|
|
---|---|---|
product name |
TeSys F
|
|
product or component type |
Contactor
|
|
device short name |
LC1F
|
|
contactor application |
Resistive load
Motor control |
|
utilisation category |
AC-4
AC-1 AC-3 |
|
poles description |
3P
|
|
power pole contact composition |
3 NO
|
|
[Ue] rated operational voltage |
<= 1000 V AC 50/60 Hz
<= 460 V DC |
|
[Ie] rated operational current |
700 A (at <40 °C) at <= 440 V AC AC-1
500 A (at <55 °C) at <= 440 V AC AC-3 |
|
motor power kW |
250 kW at 380…400 V AC 50/60 Hz (AC-3)
280 kW at 415 V AC 50/60 Hz (AC-3) 295 kW at 440 V AC 50/60 Hz (AC-3) 355 kW at 500 V AC 50/60 Hz (AC-3) 335 kW at 660…690 V AC 50/60 Hz (AC-3) 335 kW at 1000 V AC 50/60 Hz (AC-3) 147 kW at 220…230 V AC 50/60 Hz (AC-3) 80 kW at 400 V AC 50/60 Hz (AC-4) |
|
[Uc] control circuit voltage |
440 V AC 40…400 Hz
|
[Uimp] rated impulse withstand voltage |
8 kV
|
|
---|---|---|
overvoltage category |
III
|
|
[Ith] conventional free air thermal current |
700 A (at 40 °C)
|
|
rated breaking capacity |
4000 A conforming to IEC 60947-4-1
|
|
[Icw] rated short-time withstand current |
4200 A 40 °C – 10 s
3200 A 40 °C – 30 s 2400 A 40 °C – 1 min 1500 A 40 °C – 3 min 1200 A 40 °C – 10 min |
|
associated fuse rating |
500 A aM at <= 440 V
800 A gG at <= 440 V |
|
average impedance |
0.18 mOhm – Ith 700 A 50 Hz
|
|
[Ui] rated insulation voltage |
1000 V conforming to IEC 60947-4-1
1500 V conforming to VDE 0110 group C |
|
power dissipation per pole |
88 W AC-1
45 W AC-3 |
|
mounting support |
Plate
|
|
standards |
JIS C8201-4-1
IEC 60947-1 EN 60947-1 IEC 60947-4-1 EN 60947-4-1 |
|
product certifications |
LROS (Lloyds register of shipping)
DNV CB ABS CCC UL BV RMRoS RINA |
|
connections – terminals |
Control circuit: screw clamp terminals 1 cable(s) 1…4 mm²flexible without cable end
Control circuit: screw clamp terminals 2 cable(s) 1…4 mm²flexible without cable end Control circuit: screw clamp terminals 1 cable(s) 1…4 mm²flexible with cable end Control circuit: screw clamp terminals 2 cable(s) 1…2.5 mm²flexible with cable end Control circuit: screw clamp terminals 1 cable(s) 1…4 mm²solid without cable end Control circuit: screw clamp terminals 2 cable(s) 1…4 mm²solid without cable end Power circuit: bar 2 cable(s) – busbar cross section: 40 x 5 mm Power circuit: lugs-ring terminals 2 cable(s) 240 mm² Power circuit: bolted connection |
|
tightening torque |
Control circuit: 1.2 N.m
Power circuit: 35 N.m |
|
control circuit voltage limits |
Operational: 0.85…1.1 Uc 40…400 Hz (at 55 °C)
Drop-out: 0.3…0.5 Uc 40…400 Hz (at 55 °C) |
|
inrush power in VA |
1100 VA 40…400 Hz cos phi 0.9 (at 20 °C)
|
|
hold-in power consumption in VA |
18 VA 40…400 Hz cos phi 0.9 (at 20 °C)
|
|
heat dissipation |
18 W
|
|
operating time |
40…65 ms closing
100…170 ms opening |
|
mechanical durability |
10 Mcycles
|
|
maximum operating rate |
2400 cyc/h 55 °C
|
|
compatibility code |
LC1F
|