RUMC21F7 (RUMC2AB1F7)
RUMC21F7 (RUMC2AB1F7) – Universal plug-in relay – Zelio RUM – 2 C/O – 120 V AC – 10 A.
$12.00
range of product |
Zelio Relay
|
|
---|---|---|
series name |
Universal
|
|
product or component type |
Plug-in relay
|
|
device short name |
RUM
|
|
contacts type and composition |
2 C/O
|
|
[Uc] control circuit voltage |
120 V AC
|
|
[Ithe] conventional enclosed thermal current |
10 A at -40…55 °C
|
|
status LED |
Without
|
|
control type |
Lockable test button
|
|
utilisation coefficient |
20 %
|
shape of pin |
Cylindrical
|
|
---|---|---|
[Ui] rated insulation voltage |
250 V conforming to IEC
300 V conforming to CSA 300 V conforming to UL |
|
[Uimp] rated impulse withstand voltage |
4 kV
|
|
contacts material |
AgNi
|
|
[Ie] rated operational current |
10 A AC-1/DC-1 (NO) conforming to IEC
12 A at 28 V DC-1 conforming to UL 16 A at 277 V AC-1 conforming to UL 5 A AC-1/DC-1 (NC) conforming to IEC |
|
minimum switching current |
10 mA
|
|
maximum switching voltage |
250 V AC conforming to IEC
250 V DC conforming to IEC |
|
minimum switching voltage |
17 V
|
|
Resistive rated load |
10 A at 250 V AC
10 A at 28 V DC |
|
maximum switching capacity |
2500 VA AC
280 W DC |
|
minimum switching capacity |
170 mW
|
|
operating rate |
<= 18000 cycles/hour no-load
<= 1200 cycles/hour under load |
|
mechanical durability |
5000000 cycles
|
|
electrical durability |
100000 cycles for resistive load
|
|
Average coil consumption in VA |
2…3 at 60 Hz
|
|
drop-out voltage threshold |
>= 0.15 Uc AC
|
|
Operate time |
20 ms
|
|
Average coil resistance |
1700 Ohm at 20 °C +/- 15 %
|
|
rated operational voltage limits |
96…132 V AC
|
|
protection category |
RT I
|
|
safety reliability data |
B10d = 100000
|
|
operating position |
Any position
|
|
product weight |
0.085 kg
|